Group: alt.engineering.electrical
From: "Tim Perry"
Date: Tuesday, February 26, 2008 10:41 PM
Subject: Re: 240 volts


wrote in message
news:fq2htk12d7n@...
> On Wed, 27 Feb 2008 00:53:02 GMT Salmon Egg
wrote:
> | In article , phil-news-nospam@
> | wrote:
> |
> |> You have a machine that requires 240 volt three phase power. It
requires
> |> connection to 3 phase lines and ground, but not neutral. You ask your
> |> utility to supply 240 volt delta and they say no. The machine fails to
> |> operate on 208 volts. What do you do? How many different solutions
could
> |> you think of to explore?
> |
> | Do your own homework.
>
> I already did. I'm just checking to see if I missed any creative ideas
and
> to see what kind of diversity others as a group would have.
>
> --
>
|---------------------------------------/----------------------------------|
> | Phil Howard KA9WGN () / Do not send to the address below
|
> | first name lower case at / spamtrap-2008-02-26-2027@
|
>
|------------------------------------/-------------------------------------|


I actually have this issue Phil. I used a buck boost transformer. This is a
light and intermittent load. A bank of relays at the end of a long cable
run.